CPM1A Programmable Controllers Operation Manual 1784470
25 A/common (cannot be replaced by the user)
Circuit Output LED OUT
configuration
Internal OUT 24 VDC
Circuits
COM (–)
Note When using the OUT01000 or OUT01001 as a pulse output, connect dummy
resistors as required to set the load current to 0.1 to 0.2 A. If the load current is
below 0.1 A, the ON-to-OFF response time will become longer and high-speed
pulse will not be output. On the other hand, if the load current is above 0.2 A, the
transistor may generate heat and components may be damaged.
28